Power Matrix



Service: apcupsd, apcaccess
Version: 13.14.13
Attached Equipment: Smart-UPS 3000
Connection Type: USB to Chickostick
Configuration: Master/Slave
Network Port: TCP 3551

Installation

ServerVersionInstallation Method
Chickostick13.14.12 redhatyum
Poprocks13.14.13-1.fc21yum
Mallo13.14.10/usr/ports/sysutils/apcupsd
Pez13.14.8-2apt-get
Kitkat3.14.8-2apt-get
Nerds3.14.10p0pkg_add

Server Specific Notes

ServerNotes
Chickostickiptables configured to allow TCP port 3551, chkconfig apcupsd on and chkconfig --list to verify startup
Poprockschkconfig does not work out of box, used 'systemctl enable apcupsd'
Mallostartup services setup by installer
Pez/etc/default/apcupsd set ISCONFIGURED=yes
Kitkat/etc/default/apcupsd set ISCONFIGURED=yes
NerdsDownload of packages http://www.filewatcher.com/d/OpenBSD/5.1/i386/apcupsd-3.14.10p0.tgz.274168.html
saved tgz to /export/it/applications
used pkg_add apcupsd-3.14.10p0.tgz on nerds
service is launched using /usr/local/sbin/apcupsctl [start|stop|restart]

Configurations Files

/etc/apcupsd/apcupsd.conf

Master Server
UPSNAME mtups1
UPSCABLE usb
USPTYPE usb
DEVICE
UPSCLASS standalone
UPSMODE disable
BATTERYLEVEL 5
MINUTES 10

Slave Servers
UPSNAME mtups1
UPSCABLE ether
USPTYPE net
DEVICE 192.168.255.45
POLLTIME 60
BATTERYLEVEL 50
MINUTES 3
 

Notes

Verifying Device Detection and Driver
To make sure that your USB subsystem can see the UPS, just do this from a shell prompt:
cat /proc/bus/usb/devices

Verified Drivers
ls -l /sys/bus/usb/drivers/

Check Status of Service
apcaccess status

Configuration File
chickostick /etc/apcupsd/apcupsd.conf
 


Attachments

Attachments
File Last modified Size
APC_UPS_Daemon_Manual.pdf 2015-06-30 13:42 1Mb


Power Outage

Generac Generator Rated for 250A at 200V (5000W)
DevicePeak PowerNormal Power
Chicko750W350W
Poprocks1000W500W
Kitkat750W300W
Peeps1000W300W
HP 1810 Switch4.8W4W
Demarcation Equipment30W30W
Nerds60W30W
KVM20W20W
Server Monitor80W80W
Light in Server Room40W40W
Intern Isle Switch4W4W

Peak power usage leaves 741.2W remaining
Normal power usage leaves 3082W remaining

Each WS uses a workgroup switch, monitor and workstation.
Peak power usage: 129W (8 Workstations)
Normal power usage: 92W (38 Workstations)

We could also have a few lights going as we use compact florescent.

Total workstations is a theoretical max, but during the winter we have adequate power for all employees as long as we ensure that all kitchen appliances, heaters, printers, and any device not being used exclusively for work is not connected to power outlets in the back and middle offices.


CategoryITDoc